Building Envelope Systems

Envelope

Four Control Layers

LayerFunctionTypical Material
1. Water (WRB)Bulk water defenceSelf-adhered or fluid-applied membrane
2. Air barrierStops uncontrolled air movementSelf-adhered membrane, fluid-applied
3. Vapour controlManages moisture diffusion6 mil poly (≤60 ng/Pa·s·m²)
4. ThermalResists heat flowCI outboard + cavity batt

All four layers must be continuous — no gaps. Air leakage = 25–40% of heating load.

Continuous Insulation (CI)

ProductR/inchVapour PermNotes
EPSR-3.8–4.2ModerateStable R, cost-effective
XPSR-5.0LowR-value degrades over time
PolyisoR-5.7–6.5LowDerate to R-5.0 for ON winter
Mineral woolR-4.0–4.3High (open)Non-combustible, allows drying

Steel studs reduce cavity-only R-value by 40–60%. CI is mandatory (NECB).

Air Barrier — Self-Adhered Membrane

Fluid-Applied Alternative

Vapour Barrier & Batt Insulation

Vapour Barrier (6 mil Poly)

Batt Insulation

PropertyFiberglassMineral Wool
R/inchR-3.2–3.8R-3.8–4.2
MoistureAbsorbs, slow dryHydrophobic
Sound (NRC)0.90–0.950.95–1.05

No compression, no gaps, split around wires. 2% void = 10–15% R-value loss.

Window & Curtain Wall

Window Flashing Sequence

Curtain Wall

Cladding & Rain Screen

Rain Screen Principles

Cladding Types

Sub-Girt Systems

Code References

Safety & Critical Rules

Pro Tips