| Item | Value |
|---|---|
| Advance panel face | 1 1/8" HDO composite (200+ pours) |
| Panel widths | 4"–24" in 1" increments |
| Panel weight | 4.5–5.1 lbs/ft² |
| Snap tie working load | 3,000 lbs (13.3 kN) |
| Snap tie grid (fdn wall) | 600 mm H × 400–600 mm V |
| Footing form boards | 2×6 / 2×8 / 2×10 SPF #2 |
| Stakes | 2×4 × 24" min, 12" min embed |
| Stake spacing | 600 mm o.c. (≤450 deep) / 400 mm o.c. |
| Spreaders | 1×2 or 2×2 at 1200 mm o.c. |
| Chair spacing (max) | 1200 mm o.c. |
| Vapour barrier (min) | 10 mil poly; 15 mil under sensitive flooring |
| Poly lap (min) | 150 mm (recommended 300 mm), taped |
| Element | Cover |
|---|---|
| Cast against soil (no blinding) | 75 mm |
| Cast on blinding / poly | 50 mm |
| Fdn walls (ext., below grade) | 50–75 mm |
| Interior walls & columns | 30–40 mm |
| Slabs on grade (interior) | 40 mm |
| Elevated slabs (interior) | 20–30 mm |
| Bar | Class A | Class B |
|---|---|---|
| 10M | 300 mm | 390 mm |
| 15M | 450 mm | 585 mm |
| 20M | 600 mm | 780 mm |
| 25M | 750 mm | 975 mm |
| Check | Tolerance |
|---|---|
| Plan dimensions (width/length) | ± 12 mm (or +25 / −12 mm) |
| Top elevation | ± 12 mm from design |
| Plumb (vertical face) | 1:200 ratio, max 25 mm |
| Location on plan | ± 12 mm from grid |
| Anchor bolt position | ± 3 mm from design |
| Embed plate position | ± 6 mm from grid |
| Member | Min. Time (≥10°C) | Strength Req. |
|---|---|---|
| Fdn walls (vert. faces) | 12–24 hours | N/A if protected |
| Columns (vert. faces) | 12–24 hours | N/A if protected |
| Beam / slab soffits | Per P.Eng. design | 75% of f'c |
| Cantilever slab soffits | Per P.Eng. design | 100% of f'c |
Cold weather (<10°C): Extend times significantly. Do not strip unless cylinder breaks confirm strength.