| Application | Target | Range |
|---|---|---|
| Footings & foundations | 80 mm | 55–105 mm |
| Walls & columns | 100 mm | 75–125 mm |
| Pump mix (slabs) | 150 mm | 110–190 mm |
| SCC (spread test) | 550–750 mm | Per mix design |
| Max Agg. Size | Required (C-1) | Target |
|---|---|---|
| 20 mm | 5–8% | 6.5% |
| 14 mm | 6–9% | 7.0% |
| 10 mm | 6–9% | 7.5% |
| Condition | Limit |
|---|---|
| Normal placement | 10–30°C |
| Cold weather min. | 10°C |
| Hot weather max. | 35°C |
| Mass concrete max. | 70°C internal; ≤20°C differential |
| Age | Expected | Purpose |
|---|---|---|
| 7 day | 65–75% f'c | Early warning |
| 28 day | 100% f'c min | Acceptance |
| 56 day | 110–120% f'c | Blended cements |
| Exposure | Max w/c |
|---|---|
| C-1 (exterior, de-icing) | 0.40 |
| C-XL (extreme) | 0.37 |
| F-1 (interior, dry) | 0.55 |
| A-1 (agricultural) | 0.45 |
| Type | Function |
|---|---|
| Air entrainment | Freeze-thaw protection (verify every load) |
| Water reducer (A) | Reduce water 5–12%; maintain slump |
| Superplasticizer | Reduce water 12–30%; place quickly |
| Retarder (D) | Delay set 1–4 hrs; hot weather |
| Accelerator (C) | Speed set; non-chloride near rebar |
Document every rejection: photo of slump + batch ticket, reason, signature.