Concrete Testing, Precast & Specialty Work

Foundations

Slump Test (CSA A23.2-5C)

ApplicationTargetRange
Footings & foundations80 mm55–105 mm
Walls & columns100 mm75–125 mm
Pump mix (slabs)150 mm110–190 mm
SCC (spread test)550–750 mmPer mix design

Procedure

Air Content (CSA A23.1 Cl. 4.3.3)

Max Agg. SizeRequired (C-1)Target
20 mm5–8%6.5%
14 mm6–9%7.0%
10 mm6–9%7.5%

Test Methods

Temperature (CSA A23.2-17C)

ConditionLimit
Normal placement10–30°C
Cold weather min.10°C
Hot weather max.35°C
Mass concrete max.70°C internal; ≤20°C differential

Cylinder Sampling (CSA A23.2-3C)

Break Schedule

AgeExpectedPurpose
7 day65–75% f'cEarly warning
28 day100% f'c minAcceptance
56 day110–120% f'cBlended cements

Acceptance (CSA A23.1)

Mix Design & w/c Ratios

ExposureMax w/c
C-1 (exterior, de-icing)0.40
C-XL (extreme)0.37
F-1 (interior, dry)0.55
A-1 (agricultural)0.45

Key Admixtures

TypeFunction
Air entrainmentFreeze-thaw protection (verify every load)
Water reducer (A)Reduce water 5–12%; maintain slump
SuperplasticizerReduce water 12–30%; place quickly
Retarder (D)Delay set 1–4 hrs; hot weather
Accelerator (C)Speed set; non-chloride near rebar

Rejection Criteria

Document every rejection: photo of slump + batch ticket, reason, signature.

Hot & Cold Weather Limits

Hot Weather (>27°C)

Cold Weather (<5°C)