Earthwork, Grading & Compaction

Site Work

Compaction Equipment by Soil Type

SoilEquipmentAvoidPasses
Gravel (GW, GP)Smooth drum vib. (high amp)Padfoot4–6
Sand (SP, SM)Smooth drum vib. (high freq)Padfoot4–8
Silty sand (SM)Smooth drum vib.6–8
Lean clay (CL)Padfoot static/vib.Smooth drum alone6–10
Fat clay (CH)Padfoot staticAny vibratory8–12
Silt (ML)Padfoot vib. (low amp)High-amp vib.6–10
Granular A/BSmooth drum vib.Static only4–6

Max Lift Thickness (Compacted)

MaterialRide-On (≥10t)Walk-BehindRammer
Granular A200–300 mm100–150100–150
Gran. B Type I250–350 mm150–200150
Gran. B Type II300–400 mmN/RN/E
Sand (SW, GW)250–350 mm150–200150–200
Clay (CL)150–200 mmN/R100–150
Fat clay (CH)150 mm maxN/R100 max

N/R = not recommended; N/E = not effective. Loose thickness 20–35% greater.

Proctor Testing

ParameterStandard (D698)Modified (D1557)
Hammer2.5 kg / 305 mm drop4.54 kg / 457 mm drop
Layers / blows3 / 255 / 25
Energy600 kN·m/m³2,700 kN·m/m³
Typical useCohesive, residentialGranular, commercial

95% Standard ≠ 95% Modified. Modified yields 100–200 kg/m³ higher density. Always verify which standard is specified.

Field Testing Frequency (OPSS 501)

ApplicationMin. Frequency
Structural fill (footings/slabs)1 per 250 m² per lift
General site fill1 per 500 m² per lift
Trench backfill1 per 50 lin. m per lift
Granular base/subbase1 per 250 m² per lift

Nuclear Gauge Modes

Ontario Granular Specs (OPSS.MUNI 1010)

Typical Church Pavement Section

150 mm Gran. A over 300 mm Gran. B Type I over prepared subgrade.

Under Building Slab

150–200 mm Gran. A over compacted structural fill.

Bearing Capacity (OBC Table 9.4.4.1)

Soil / RockkPa
Sound rock (granite, limestone)500
Dense gravel / sand-gravel150
Compact coarse sand100
Loose fine sand / stiff clay50–75
Soft clay / silt25

Frost Depths (OBC)