| Item | Value |
|---|---|
| EMT deduct ¾" | 6" (stub-up) |
| EMT deduct 1" | 8" (stub-up) |
| 30° offset multiplier | 2× depth; shrink ¼"/in |
| 22.5° offset multiplier | 2.6× depth; shrink 3/16"/in |
| 3-point saddle | 45° centre + two 22.5° returns |
| EMT support spacing | 1.5 m max; within 1.5 m of box |
| Rigid support spacing | Up to 3 m (size-dependent) |
| Expansion fittings | Every 30 m & at bldg exp. joints |
| 1 conductor | 53% max |
| 2 conductors | 31% max |
| 3+ conductors | 40% max (target 30% for runs >15 m) |
| System | A / B / C | Neutral | Ground |
|---|---|---|---|
| 120/208V | Blk / Red / Blue | White | Green/bare |
| 347/600V | Org / Brn / Yel | Wht w/ stripe | Green |
| Isolated gnd | — | — | Green/yellow |
| Total (service to outlet) | 5% max |
| Branch circuit | 3% max |
| Connection | Torque |
|---|---|
| 15A/20A receptacles & switches | 1.6–2.0 N·m (14–18 in-lb) |
| Branch breaker terminals | 2.5–5.0 N·m (per mfr.) |
| Large lugs (100A+) | 30–50 N·m (per mfr.) |
Aluminum: Anti-oxidant compound required on all terminations.