Electrical Power & Distribution

Mech/Elec

Conduit Bending & Installation

ItemValue
EMT deduct ¾"6" (stub-up)
EMT deduct 1"8" (stub-up)
30° offset multiplier2× depth; shrink ¼"/in
22.5° offset multiplier2.6× depth; shrink 3/16"/in
3-point saddle45° centre + two 22.5° returns
EMT support spacing1.5 m max; within 1.5 m of box
Rigid support spacingUp to 3 m (size-dependent)
Expansion fittingsEvery 30 m & at bldg exp. joints

Conduit Fill (OESC)

1 conductor53% max
2 conductors31% max
3+ conductors40% max (target 30% for runs >15 m)

Conduit Selection

Conductor Colour Coding (OESC)

SystemA / B / CNeutralGround
120/208VBlk / Red / BlueWhiteGreen/bare
347/600VOrg / Brn / YelWht w/ stripeGreen
Isolated gndGreen/yellow

Voltage Drop (OESC 8-102)

Total (service to outlet)5% max
Branch circuit3% max

Termination Torque Values

ConnectionTorque
15A/20A receptacles & switches1.6–2.0 N·m (14–18 in-lb)
Branch breaker terminals2.5–5.0 N·m (per mfr.)
Large lugs (100A+)30–50 N·m (per mfr.)

Aluminum: Anti-oxidant compound required on all terminations.

Panels & Distribution

Emergency & Exit Lighting

Grounding & Bonding

Underground Electrical

Code References

Safety — Do Not Forget

Pro Tips