| Item | Value |
|---|---|
| Smoke detector spacing | 1 per 84 m² (smooth ceiling) |
| Heat det. — fixed temp | 57°C (general) or 93°C (high-heat) |
| Heat det. — rate-of-rise | Activates at > 8.3°C/min |
| Pull station height | 1050–1200 mm AFF; ≤ 1.5 m from exit |
| Battery capacity | 24-hr standby + 5-min alarm |
| Circuit survivability | 1-hr rated conduit or CI cable |
| Conduit & box colour | Red; labelled “FIRE ALARM” |
| FACP power | Dedicated ckt, lockable red-handle bkr |
| Cable | Speed / Distance |
|---|---|
| Cat6 | 1 Gbps / 100 m |
| Cat6A | 10 Gbps / 100 m |
| Fibre OM3/OM4 | 10+ Gbps / ≤ 300 m |
| Singlemode fibre | Unlimited BW / long distance |
| UTP max pull tension | 110 N (25 lbf) |
| Min bend radius — Cat6 | 4× cable diameter |
| Min bend radius — Cat6A | 6× cable diameter |
| Data/power parallel sep. | 200 mm (8″) min |
| Data/power crossings | 90° only |
| Wiring standard | T568B consistently |
| Telecom room min size | 3 m × 3 m, climate-controlled |
| Item | Requirement |
|---|---|
| Support spacing | 1.5–3 m (type/load dependent) |
| Single-cond. fill (ladder) | 40% max cross-section |
| Data fill (wire basket) | 50% max (BICSI) |
| Power/data separation | Separate trays, 300 mm vertical min |
| Bonding | Every splice; continuous ground path (OESC) |