Fire Alarm, Data & Building Systems

Mech/Elec

Fire Alarm (CAN/ULC-S524)

ItemValue
Smoke detector spacing1 per 84 m² (smooth ceiling)
Heat det. — fixed temp57°C (general) or 93°C (high-heat)
Heat det. — rate-of-riseActivates at > 8.3°C/min
Pull station height1050–1200 mm AFF; ≤ 1.5 m from exit
Battery capacity24-hr standby + 5-min alarm
Circuit survivability1-hr rated conduit or CI cable
Conduit & box colourRed; labelled “FIRE ALARM”
FACP powerDedicated ckt, lockable red-handle bkr

Verification (CAN/ULC-S537)

Data & Communications Cabling

CableSpeed / Distance
Cat61 Gbps / 100 m
Cat6A10 Gbps / 100 m
Fibre OM3/OM410+ Gbps / ≤ 300 m
Singlemode fibreUnlimited BW / long distance

Installation Limits

UTP max pull tension110 N (25 lbf)
Min bend radius — Cat64× cable diameter
Min bend radius — Cat6A6× cable diameter
Data/power parallel sep.200 mm (8″) min
Data/power crossings90° only
Wiring standardT568B consistently
Telecom room min size3 m × 3 m, climate-controlled

Security Systems

Church-Specific

Cable Tray & Solar PV

Cable Tray

ItemRequirement
Support spacing1.5–3 m (type/load dependent)
Single-cond. fill (ladder)40% max cross-section
Data fill (wire basket)50% max (BICSI)
Power/data separationSeparate trays, 300 mm vertical min
BondingEvery splice; continuous ground path (OESC)