Specialties — Ceilings, Accessories & Access Flooring

Finishes

ACT Grid Specifications

ItemSpecification
Hanger wire (standard)#12 ga. — 56 kg (125 lbs) safe load
Hanger wire (heavy)#10 ga. — for heavy fixtures/gypsum-backed tiles
Wire spacingMax 1200 mm o.c. along main runners
Wire at splicesWithin 150 mm of every main-runner splice
Wire at fixturesWithin 150 mm each side of heavy items
Wire turnsMin. 3 full turns at each connection
Wall angle fastening400 mm o.c. max into studs or CMU
Grid level tolerance± 3 mm across room (CISCA)
Border tile minimum≥ 300 mm (half of 600 mm tile)
Plenum clearanceMin 75 mm above grid for tile insertion

Acoustic Tile Performance

Tile TypeNRCCACUse
Standard Lay-In0.50–0.7025–35Offices, corridors
Tegular (Reveal)0.55–0.7530–40Fellowship halls, classrooms
High-NRC Acoustic0.80–0.9535–42Music rooms, worship overflow
Concealed Spline0.50–0.6525–35Lobbies (monolithic look)
Gypsum-Backed0.55–0.6540–50Sound-sensitive adjacencies

NRC: Sound absorption (higher = more). CAC: Sound blocking between rooms via plenum (higher = better).

Church Acoustic Targets

Washroom Mounting Heights (OBC/AODA)

AccessoryHeight (AFF)
Grab bars (side & rear)840–860 mm to centre
Soap dispenser900–1100 mm
Paper towel dispenser900–1200 mm
Hand dryer activation900–1100 mm
Mirror bottom edgeMax 1000 mm (accessible)
Coat hook1200 mm (accessible)
Baby change station (open)860 mm deck height
Max forward reach (AODA)1200 mm

Accessible Stall (OBC 3.8)

Access Flooring

GradeConc. LoadApplication
CISCA Grade 11,000 N (225 lbs)Offices, meeting rooms
CISCA Grade 22,000 N (450 lbs)AV rooms, equipment racks
CISCA Grade 34,500 N (1,000 lbs)Server rooms

Code & Standard References

Safety & Critical Rules

Pro Tips