Steel Stud & Heavy Gauge Framing

Structure

Light-Gauge Selection

GaugemmApplication
25ga0.45Light partitions ≤3.0 m
22ga0.68Standard commercial ≤4.0 m
20ga0.84Tall walls ≤5.5 m, fire-rated
18ga1.09Heavy commercial, structural transition

Heavy-Gauge (Structural CFS)

GaugemmApplication
18ga1.09Light load-bearing, curtain wall infill
16ga1.37Standard load-bearing, ext. curtain wall
14ga1.73Heavy load-bearing, multi-storey
12ga2.46Headers, jambs, tall curtain wall

Structural = 345 MPa (50 ksi). Non-structural = 228 MPa (33 ksi). Verify stamp!

Tolerances & Spacing

ItemValue
Default spacing (church)400 mm o.c. recommended
600 mm o.c.Non-rated partitions ≤3.0 m only
300 mm o.c.Very tall walls, tight curves
Stud spacing tolerance± 3 mm from layout
Plumb toleranceMax 3 mm in 3 m
Track alignment (top/bottom)Within 3 mm
Stud cut short of height~10 mm (non-load-bearing)
PAF spacing (floor track)600 mm o.c., 150 mm from ends

Bridging Requirements

Wall HeightRows
>2.4 m1 row at mid-height
>3.6 m2 rows at third points
>4.8 m3 rows evenly spaced

Fire-Rated Assemblies (ULC)

RatingTypical Assembly
1-hr (U411)92mm, 22ga @ 600 o.c., 1 layer 15.9mm Type X each side, mineral wool
2-hr (U412)92mm, 20ga @ 400 o.c., 2 layers 15.9mm Type X each side, mineral wool

Sound Ratings (STC) — Church Spaces

AdjacencySTC
Sanctuary to classroom55–60
Between classrooms45–50
Sanctuary to lobby50–55
Office to office45–50
Nursery to adjacent50–55
Mech. room to occupied55–60

Double-stud wall (2 rows, 25mm gap, 2 layers each side, mineral wool) = STC 60–65.

Deflection Head Tracks

Fastener Guide

ScrewUse
TEK 1 (fine point)Steel-to-steel ≤22ga
TEK 3 (drill point)20ga–14ga connections
TEK 5 (long drill)14ga–10ga, clip angles
Wafer headStud-to-track (flush for drywall)
HWH (hex washer)Structural, clips, bridging
Type S drywallDrywall to steel studs

Drywall screws: 200 mm edges, 300 mm field. Confirm against ULC listing.

Safety — Do Not Forget

Pro Tips